  4. RD30 Male angled connector, Contacts: 4+PE, 12.0-14.0 mm, unshielded, screw clamp, IP65, ESTI+, VDE
Part no.: 99 0709 72 05

RD30 Male angled connector, Contacts: 4+PE, 12.0-14.0 mm, unshielded, screw clamp, IP65, ESTI+, VDE

RD30, series 694, Power Connectors
Available numbers of contacts
Compare product
Downloads
General features
Moreless
Part no. 99 0709 72 05
Connector design Male angled connector
Version Connector pin angled
Connector locking system screw
Termination screw clamp
Degree of protection IP65
Cross-sectional area 2.50 mm² / AWG 14
Cable outlet 12.0-14.0 mm
Twistability 45° (8 coding options)
Temperature range from/to -40 °C / 100 °C
Mechanical operation > 500 Mating cycles
Weight (g) 87.84
Customs tariff number 85369010
Country of Origin DE
Rated voltage 400 V
Rated impulse voltage 6000 V
Rated current 20.0 A
Insulation resistance ≥ 1010 Ω
Pollution degree 3
Overvoltage category III
Insulating material group III
EMC compliance unshielded
Housing material PA
Contact body material PA (UL94 HB)
Contact material CuZn (brass)
Contact plating Ag (silver)
REACH SVHC CAS 96-45-7 (Imidazolidine-2-thione)
CAS 7439-92-1 (Lead)
SCIP number d35bcd96-664d-4a3e-a1fd-ba1c2f834b7a
Approvals ESTI+, VDE
eCl@ss 11.1 27-44-01-02
ETIM 9.0 EC002635
Low Voltage Directive 2014/35/EU (EN 60204-1:2018;EN 60529:1991)
General Disclaim Notice
  1. The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
  2. The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
  3. To protect against unintentional opening of the connector, the thread between the housing and the connector head must be secured with a suitable cyanoacrylate adhesive when used in circuits with voltages dangerous to the touch. This does not apply to connectors used in SELV and PELV circuits according to IEC 61140 (EN 61140, VDE 0140-1).
  4. Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
  5. The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
  6. Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
  7. The plug connector is not suitable for mains voltages Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".
  8. To lock the cable connector to the device connector, we recommend tightening the threaded ring to 1 Nm. A suitable torque wrench is available as an accessory (order no. 07 0082 000).
Downloads
Data sheet
Data sheet 99 0709 72 05
PDF
Data sheet, Data sheet 99 0709 72 05
Certificates
VDE certificate
PDF, 331.25 KB
REACH
99 0709 72 05
PDF
RoHS
99 0709 72 05
PDF
China RoHS
99 0709 72 05
PDF
Declaration of conformity, Low Voltage Directive
Declaration of conformity
Low Voltage Directive
PDF
UKCA declaration of conformity, Electrical Equipment
UKCA declaration of conformity
Electrical Equipment
PDF
CAD files
Select required format
RD30 Power
99 0709 72 05