Part no.: 99 9687 809 08
RJ45 connector, Contacts: 8, 5.0-9.0 mm, shieldable, Piercing technology, IP20
RJ45, series 825, Automation Technology - Data Transmission
This RJ45 connector mit Rast-Verriegelung and a pin count of 8 is according to its protection class IP20 Protected against solid foreign bodies. No protection against water. It can be used in areas with a pollution degree of 2. In places where light, non-conductive soiling may occur, but temporary conductivity due to condensation must be expected in some cases. With temperatures ranges of -40 °C/85 °C is this shieldable M12-X RJ45 connector designed for both severe cold and severe heat. und has the UL approval. Due to the qualified rated voltage of 50 V DC and the rated current of 1,3 A it is perfectly tuned for its field of application.
General features
MorelessPart no. | 99 9687 809 08 |
Connector design | connector |
Connector locking system | lock |
Termination | Piercing technology |
Degree of protection | IP20 |
Cross-sectional area | AWG 26-24/1, AWG 27-24/7 |
Cable outlet | 5.0-9.0 mm |
Temperature range from/to | -40 °C / 85 °C |
Mechanical operation | > 750 Mating cycles |
Connection standard | TIA 568B AWG 27 - 24 |
Weight (g) | 23.03 |
Customs tariff number | 85366990 |
Country of Origin | TW |
Electrical parameters
MorelessRated voltage | 50 V DC |
Rated current | 1.3 A |
Pollution degree | 2 |
Transmission rate | CAT 6A |
Overvoltage category | III |
Insulating material group | IIIa |
EMC compliance | shieldable |
Shield connection | Shield clamping |
Material
MorelessHousing material | Zinc die-cast nickel-plated |
Contact body material | PC |
Contact material | Spring steel |
Contact plating | Au (gold) |
REACH SVHC |
None (No pollutants) |
SCIP number | SCIP-number not available |
Classifications
MorelesseCl@ss 11.1 | 27-44-01-02 |
ETIM 9.0 | EC002635 |
General Disclaim Notice
- The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
- The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
- Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
- The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
- Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
- The plug connector is not suitable for mains voltages Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".
- To lock the cable connector with the device connector, the threaded ring is tightened "hand-tight" (approx. 60 cNm).
Downloads
Data sheet
Data sheet 99 9687 809 08
download
REACH
99 9687 809 08
download
RoHS
99 9687 809 08
download
China RoHS
99 9687 809 08
download
CAD files
Select required format